Moisture Removal Rate*:             84.5 Lbs./Hr.

                                                            14.7 Lbs./Hr.

Fresh Air Volume Required:            6000 CFM @ 0.5” E.S.P.

                                                            Must be field balanced.

Recirculation Air:                             6000 CFM @ 0.5” E.S.P.

May need to upsize the supply fan motor for external static pressure above 0.5”.

Electrical Requirements:

Components

H.P.

Single Phase

Three Phase

Three Phase

Three Phase

 

 

240V / 1 / 60

208V / 3 / 60

230V / 3 / 60

460V / 3 / 60

HIGH VOLTAGE

 

 

 

 

 

Supply Fan VFD

5.0

N/A

19.6

17.1

8.6

Exhaust Fan VFD

5.0

 

19.6

17.1

8.6

 

Unit FLA

 

39.2

34.2

17.2

 

WSA

 

44.1

38.5

19.2

 

OPD

 

60

50

30

CONTROL VOLTAGE

 

N/A

120V/1/60

120V/1/60

120V/1/60

Transformer 75 V.A

 

 

.63

.63

.63

Transformer 50 V.A

 

 

.42

.42

.42

 

Unit FLA

 

1.05

1.05

1.05

 

WSA

 

1.2

1.2

1.2

 

OPD

 

20

20

20

 

Motor and Fan Data:

H.P.

208 Volts

230 Volts

460 Volts

P.F.

Efficiency

3

8.3

7.5

3.8

0.836

89.4

5

13.6

12.3

6.2

0.865

88.4

7.5

20.6

18.6

9.3

0.830

90.9

10

26.3

23.8

11.9

0.862

91.3

 

Mechanical Information:

Unit Total Heating Capacity:            362 MBH

Unit Net Heating Capacity:            324 MBH

Condensate Drain:  1-¼” M.P.T.

Return Air Inlet:  30”W x 24”H

Fresh Air Inlet:  36”W x 24”H

Supply Air Outlet:  30”W x 24”H

Exhaust Air Outlet:  20”W x 20”H

Water Inlet:  2” O.D. sweat connection

Water Outlet: 2” O.D. sweat connection

Water Flow:  36.7 GPM

 

* -        (60% RH, 67ºF Dew Point) indoor conditions               (62% RH, 59ºF Dewpoint) outdoor conditions

(50% RH, 61ºF Dew Point) indoor conditions               (62% RH, 59ºF Dewpoint) outdoor conditions