Moisture Removal Rate*:             253.5 Lbs./Hr.

                                                            44.1 Lbs./Hr.

Fresh Air Volume Required:            18000 CFM @ 1.0” E.S.P.

                                                            Must be field balanced.

Recirculation Air:                             18000 CFM @ 1.0” E.S.P.

May need to upsize the supply fan motor for external static pressure above 1.0”.

Electrical Requirements:

Components

H.P.

Single Phase

Three Phase

Three Phase

Three Phase

 

 

240V / 1 / 60

208V / 3 / 60

230V / 3 / 60

460V / 3 / 60

HIGH VOLTAGE

 

 

 

 

 

Supply Fan VFD

20.0

N/A

67.4

61.0

30.5

Exhaust Fan VFD

20.0

 

67.4

61.0

30.5

 

Unit FLA

 

134.8

122.0

61.0

 

WSA

 

151.7

137.3

68.6

 

OPD

 

200

175

100

CONTROL VOLTAGE

 

N/A

120V/1/60

120V/1/60

120V/1/60

Transformer 75 V.A

 

 

.63

.63

.63

Transformer 50 V.A

 

 

.42

.42

.42

 

Unit FLA

 

1.05

1.05

1.05

 

WSA

 

1.2

1.2

1.2

 

OPD

 

20

20

20

 

Motor and Fan Data:

H.P.

208 Volts

230 Volts

460 Volts

P.F.

Efficiency

10

26.3

23.8

11.9

0.862

91.3

15

41.0

37.0

18.5

0.815

93.0

20

52.4

47.3

23.7

0.847

93.5

25

66.4

60.0

30.0

0.830

94.1

 

Mechanical Information:

Unit Total Heating Capacity:            1233 MBH

Unit Net Heating Capacity:            1120 MBH

Condensate Drain:  1-¼” M.P.T.

Return Air Inlet:  48”W x 36”H

Fresh Air Inlet:  72”W x 30”H

Supply Air Outlet:  48”W x 36”H

Exhaust Air Outlet:  36”W x 36”H

Water Inlet:  3-½” O.D. sweat connection

Water Outlet: 3-½” O.D. sweat connection

Water Flow:  120 GPM

 

* -        (60% RH, 67ºF Dew Point) indoor conditions               (62% RH, 59ºF Dewpoint) outdoor conditions

(50% RH, 61ºF Dew Point) indoor conditions               (62% RH, 59ºF Dewpoint) outdoor conditions