Moisture Removal Rate*:             126.7 Lbs./Hr.

                                                            22.0 Lbs./Hr.

Fresh Air Volume Required:            9000 CFM @ 1.0” E.S.P.

                                                            Must be field balanced.

Recirculation Air:                             9000 CFM @ 1.0” E.S.P.

May need to upsize the supply fan motor for external static pressure above 1.0”.

Electrical Requirements:

Components

H.P.

Single Phase

Three Phase

Three Phase

Three Phase

 

 

240V / 1 / 60

208V / 3 / 60

230V / 3 / 60

460V / 3 / 60

HIGH VOLTAGE

 

 

 

 

 

Supply Fan VFD

10.0

N/A

35.1

31.8

15.9

Exhaust Fan VFD

7.5

 

28.2

25.5

12.8

 

Unit FLA

 

63.3

57.3

28.7

 

WSA

 

72.1

65.3

32.7

 

OPD

 

100

80

40

CONTROL VOLTAGE

 

N/A

120V/1/60

120V/1/60

120V/1/60

Transformer 75 V.A

 

 

.63

.63

.63

Transformer 50 V.A

 

 

.42

.42

.42

 

Unit FLA

 

1.05

1.05

1.05

 

WSA

 

1.2

1.2

1.2

 

OPD

 

20

20

20

 

Motor and Fan Data:

H.P.

208 Volts

230 Volts

460 Volts

P.F.

Efficiency

5

13.6

12.3

6.2

0.865

88.4

7.5

20.6

18.6

9.3

0.830

90.9

10

26.3

23.8

11.9

0.862

91.3

15

41.0

37.0

18.5

0.815

93.0

 

Mechanical Information:

Unit Total Heating Capacity:            603 MBH

Unit Net Heating Capacity:            547 MBH

Condensate Drain:  1-¼” M.P.T.

Return Air Inlet:  36”W x 30”H

Fresh Air Inlet:  52”W x 24”H

Supply Air Outlet:  36”W x 30”H

Exhaust Air Outlet:  24”W x 24”H

Water Inlet:  2-½” O.D. sweat connection

Water Outlet: 2-½” O.D. sweat connection

Water Flow:  60 GPM

 

* -        (60% RH, 67ºF Dew Point) indoor conditions               (62% RH, 59ºF Dewpoint) outdoor conditions

(50% RH, 61ºF Dew Point) indoor conditions               (62% RH, 59ºF Dewpoint) outdoor conditions